Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01529
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/02/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 04/02/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/05/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/08/2004 | NEAL SAUNDERS | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/08/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/08/2004 | JIM EGAN | FIRE | REVIEW | Approv-Cond | Verfication must be provided to indicate that existing fire sprinkler system design is adequate to protect Rack Storage of Class 3 Commodity to 20 feet storage height prior to storage racks being installed. |
| 04/08/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/08/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM01529 DENIED 4/5/04 1. Clarify how overload protection is to be provided for CU-1. |
| 04/08/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the condensate drain for HP-1 so that the termination point is in the space controlled by tenant of Suite 101. Reference Section 807.2, UPC 1994. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/23/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |