Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM01415
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/21/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/21/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM01415 DENIED 4/21/04 1. Feeder to Panel LPL, #3, has ampacity of 100 according to NEC Table 310-16 75 degree C column. Not protected by 150A cb per NEC 240-3. 2. Per NEC 240-21 (c) (2) (a) (2), the ampacity of the secondary conductors in this configuration shall be not less than the rating of the overcurrent protective device at the termination of the secondary conductors. SPL is rated for 150A. The Conductor is rated for 100A. 3. Per NEC Table 450-3(b), primary protection shall not exceed 250% of transformer rated current. 25,000/(1.73)(480) = 30. (30)(2.5) = 75, which is less than the 80A CB in Panel HB. 4. Parking lot lighting on Panel HB totals 43 KVA. (43)(0.25) = 10.75. 10.75 + 426.74 = 436.99. This is close to 433.99, which is NEC 200 feeder load, but only accounts for the parking lot lights as continuous load. Please provide full breakout of all loads and diversity factors applicable to this calculation. 5. Please have the plans engineered and sealed by an Electrical Engineer registered in the State of Arizona. See the 1997 Uniform Administrative Code 302.2. |
04/21/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/04/2004 | NSAUNDE1 | OUT TO CUSTOMER | Completed |
05/04/2004 | NSAUNDE1 | REJECT SHELF | Completed |