Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM01415
Parcel: 105102420

Address:
455 E WETMORE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01415
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2004 JIM EGAN FIRE REVIEW Approved
03/26/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Resolve how the DWV (detail 3/P1) is to be handled in this project: sump pump or direct connection?
2. If the sump pump is to be used, how is it to connect to the sewer system?
3. What is the termination point of the T&P relief from the water heater? A floor drain is not approved for this purpose unless it has a funnel to prevent splashing.
4. Clarify what equipment is new and what is existing.
03/26/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
03/26/2004 ROBERT SHERRY WATER REVIEW Approved
03/26/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
03/26/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/26/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM01415 DENIED 3/26/04
1. provide disconnect for WH per NEC 422 Part C.
2. Provide conduit and conductor size for LPL feeder and TPL secondary.
3. Locate all equipment in plan view, such as TPL, SPL, and the existing panel feeding TPL.
4. It appears that equipment TPL on the Enclosed Circuit Breaker Schedule should read "SPL". Please clarify.
5. Provide load calculations for the panel feeding TPL, and that of the service, as necessary.
03/26/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/21/2004 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2004 TAMI ACHONG OUT TO CUSTOMER Completed