Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM01393
Parcel: 103090670

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01393
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2004 JIM EGAN FIRE REVIEW Approved
03/25/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
03/25/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
03/26/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the water piping was sized and that it does not cause the existing system to be overloaded. Reference Sections 101.5.1 and 610.1, UPC 1994,
03/26/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM01393 DENIED 3/16/04
Provide load calculations for service.
03/26/2004 ROBERT SHERRY WATER REVIEW Approved
03/26/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise outside air calculations using the occupant loading values form Table 403.3, IMC 2000.
2. Calculate the required total amout of ventilation for AC unit 3 using the method shown in Section 403..3.2, IMC 2000.
04/13/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/13/2004 LLESNY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2004 LISA LESNY OUT TO CUSTOMER Completed