Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01393
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/25/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
03/25/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/25/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
03/26/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the water piping was sized and that it does not cause the existing system to be overloaded. Reference Sections 101.5.1 and 610.1, UPC 1994, |
03/26/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM01393 DENIED 3/16/04 Provide load calculations for service. |
03/26/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/26/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise outside air calculations using the occupant loading values form Table 403.3, IMC 2000. 2. Calculate the required total amout of ventilation for AC unit 3 using the method shown in Section 403..3.2, IMC 2000. |
04/13/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
04/13/2004 | LLESNY1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/13/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |