Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01390
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/25/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/25/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/25/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 03/25/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/25/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 03/25/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/31/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/31/2004 | CAGUILA1 | WWM | REVIEW | Passed | |
| 03/31/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM01390 DENIED 3/25/04 1. Load Calculation Note 5: if existing load is 1931 A, please demonstrate how the addition of 9 amps totals a new load of 1746 A. 2. Load Calculation Note 2: suggest that Pnl IEPB has a connected load of 135A, not 1353. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/05/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 04/02/2004 | SUE REEVES | APPROVAL SHELF | Completed |