Permit Number: T04CM01381
Parcel: 12414115A

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T04CM01381
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
05/20/2004 ROBERT SHERRY WATER REVIEW Approved
05/20/2004 GP 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed
05/21/2004 JIM EGAN FIRE REVIEW Denied Provide fire sprinklers throughout or provide minimum 2-hr horizontal fire rated separation to separate E-Occupancy from R-1 Occupancy. To qualify as unseparated uses the building must conform to the most restrictive occupancy, The Tucson Building and Fire Code requires fire sprinklers throughout all E-Occupancies more than one-story in height.
05/25/2004 MELISSA POULIN WWM REVIEW Needs Review
05/25/2004 EGRANT1 ZONING REVIEW Needs Review
05/25/2004 EGRANT1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/25/2004 EGRANT1 OUT TO CUSTOMER Completed