Permit Number: T04CM01379
Parcel: 103090670

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01379
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2004 JIM EGAN FIRE REVIEW Approved
03/25/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the water piping was sized and that it does not cause the existing system to be overloaded. Reference Sections 101.5.1 and 610.1, UPC 1994,
03/25/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
03/25/2004 ROBERT SHERRY WATER REVIEW Approved
03/25/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
03/25/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations. Reference Section 404, IMC 2000.
2. Clarify how fan coil units FC-1 and FC-2 are to receive 100 cfm of outside air from the supply air of AC-1.
3. Does AC-1 have a smoke detector in the return duct?
03/25/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
03/26/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM01379 DENIED 3/26/04
Provide service load calculations.
04/13/2004 LLESNY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2004 LISA LESNY OUT TO CUSTOMER Completed