Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01379
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/25/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/25/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the water piping was sized and that it does not cause the existing system to be overloaded. Reference Sections 101.5.1 and 610.1, UPC 1994, |
| 03/25/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/25/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/25/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 03/25/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation calculations. Reference Section 404, IMC 2000. 2. Clarify how fan coil units FC-1 and FC-2 are to receive 100 cfm of outside air from the supply air of AC-1. 3. Does AC-1 have a smoke detector in the return duct? |
| 03/25/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 03/26/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM01379 DENIED 3/26/04 Provide service load calculations. |
| 04/13/2004 | LLESNY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/13/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |