Permit Number: T04CM01376
Parcel: 11706320C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01376
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
03/25/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide calculations to show that the exposed piping is adequately protected from freeezing or provide means to drain the piping during the winter.
03/25/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved Needs second set. Technical/Code requirements OK.
03/25/2004 ROBERT SHERRY WATER REVIEW Approved
03/25/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
03/25/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show size, route, and termination of the drains from the evaporative coolers.
04/13/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
04/13/2004 MELISSA POULIN WWM REVIEW Approved
04/13/2004 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2004 LISA LESNY OUT TO CUSTOMER Completed