Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2004 Christy Foreman BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS PROJECT #T04CM01208
04/07/2004 4179 S Boulderfield Pl.


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.
SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical codes. All code references are to the 2000 IRC and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
1. Note that the current residential building code adopted by the City of Tucson is the 2000 IRC. All references to the building code are 2000 IRC unless noted otherwise.
2. All plans shall be legible and a scale no smaller than ΒΌ inch = 1-foot shall be used for all floor plans, framing plans and elevations. Details and cross sections shall be a minimum 3/8 inch = 1-foot scale.
3. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints.
4. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
5. List the square footage for all the following areas separately on the drawings:
- Livable area
- garage
- porch / patio covers
- decks
6. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

STRUCTURAL PLANS:
Provide complete roof and floor framing plans.
Framing details to carry load down to footings @ Dining Room Entry.
Show beam / header size @ dining room entry.
Wall to roof framing connections. Ledger or bearing on wall?
Post & Beam @ porch connection.
Detail 9/7 does not match floor plan
Detail 10/7 Clarify ledger attachment. Rafter size. Nail attachment specified is inadequate.
Elevation of tower entry & floor plan do not match. Details for framing need to be provided.

1. Show details for all bearing and critical non-bearing conditions.
ELEVATIONS:
1. Note and dimension that the fireplace chimney must terminate a minimum of 2' above any point of roof within 10' measured horizontally and not less than 3' above the point where the chimney passes through the roof, per R1001.6.
2ft was noted per code. It should be 3 ft where chimney passes through the roof.
PLUMBING PLANS:
1. Water line: Provide the total fixture unit demand and maximum developed length. Locate meter and show water main size.
Length is not accurate and is undersized for the amount of fixtures.
If you have any questions, please contact your assigned plans examiner Christy Foreman at 791-5550, extension 1113.