04/01/2004 Christy Foreman BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS PROJECT #T04CM01208
04/07/2004 4179 S Boulderfield Pl.


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.
SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical codes. All code references are to the 2000 IRC and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
1. Note that the current residential building code adopted by the City of Tucson is the 2000 IRC. All references to the building code are 2000 IRC unless noted otherwise.
2. All plans shall be legible and a scale no smaller than ΒΌ inch = 1-foot shall be used for all floor plans, framing plans and elevations. Details and cross sections shall be a minimum 3/8 inch = 1-foot scale.
3. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints.
4. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
5. List the square footage for all the following areas separately on the drawings:
- Livable area
- garage
- porch / patio covers
- decks
6. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.
SITE PLAN: (NOT REQUIRED FOR MODEL PLANS)
1. Indicate the location of gas, water, electric and sewer or septic line on the property, and where they enter the building. Provide the location of your water meter and septic system if it exists.
FOUNDATION PLANS:
1. Locate and specify all anchor-bolt 7" embedment into concrete or masonry. Maximum spacing 6' O.C. and within 12" of each end of sill plate per R403.1.6.
FLOOR PLANS:
1. Appliances installed in garages shall be mounted on platforms at least 18" above the floor, per M1307.3.
STRUCTURAL PLANS:
1. Provide complete roof and floor framing plans. Show size, spacing and span of all framing members beams.
Provide beam size at Living Room / Kitchen, Dining room / Entry, Living Room / Entry.
(3) 2x8 @ entry between living room and dining room appears to be undersized.


2. Provide manufacturer's calculations and data for pre-fabricated trusses and glue-lam beams. Truss calculations must be signed, dated and wet-sealed by an engineer who is registered in Arizona. Truss calculations shall be cross-referenced to toe floor plans. The engineer of record shall review and "SHOP DRAWING" stamp approval on truss calculations. I would like to review recommended framing from truss manufacturer to verify location of bearing points.
3. Specify lateral support of trusses.
4. Completely detail all connections and cross-reverence to the foundation and framing plans:
- Hold-down locations and types - PAHD42 does not provide adequate capacity in all situations for end stud.

5. Show details for all bearing and critical non-bearing conditions.
6. Provide brace wall details and notes for exterior frame walls and main cross-stud partitions, or use fully braced, per R602.10.3. A minimum panel width of 48" is required to effectively brace the partition. See table R602.10.3, category "C". If bracing does not comply, provide a lateral analysis or alternate design to be reviewed by the plan examiner. Wind forces for single story residences shall use 90 MPH, exposure "B". Two story residences or areas of higher wind shall use exposure "C".
Provide structural analysis. Prescriptive method only allows 10 ft. max height of roof diaphragm.
ELEVATIONS:
1. Note and dimension that the fireplace chimney must terminate a minimum of 2' above any point of roof within 10' measured horizontally and not less than 3' above the point where the chimney passes through the roof, per R1001.6.
SECTIONS - DETAILS - MISC. NOTES:
1. Wood sill plates shall be foundation grade redwood or pressure-treated wood per R324. Note on details.
2. Note and specify the length of anchor bolts for sill plates, top plates and ledgers.
3. Note slab is 6" above grade.
PLUMBING PLANS:
1. Water line: Provide the total fixture unit demand and maximum developed length. Locate meter and show water main size
MECHANICAL PLANS:
1. Gas appliances shall comply with ARIZONA STATE PLUMBING CODE combustion air requirements. Detail how you will comply.
ELECTRICAL PLANS:
1. All receptacle outlets in bathrooms, kitchens, unfinished basements, garages or carports, at grade level and within 6' of a wet bar or kitchen sink shall have ground fault circuit interrupting protection. Note on the drawings at each outlet requiring such protection, per E3802. Laundry room sink.
If you have any questions, please contact your assigned plans examiner Christy Foreman at 791-5550, extension 1113.

NOTE: As of 2-02-01 the City of Tucson has adopted the 2000 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code. All model plans shall reference these codes.
04/08/2004 GERRY KOZIOL WWM REVIEW Approved