Permit Number: T04CM01199
Parcel: 13355230A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01199
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2004 JIM EGAN FIRE REVIEW Approved
03/15/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/15/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
03/15/2004 ROBERT SHERRY WATER REVIEW Approved
03/15/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
03/15/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/16/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TO4CM01199 DENIED 3/16/04

1. For the fans on TJ-25,27 and TJ-33,35, (3) (1.25) =4.12. The fuse size to use is 6 per NEC 240-6. Or justify otherwise.
2. For the refrig on TJ-21,23, (9.1) (1.25) =11.4. The fuse size to use is 15 per NEC 240-6. Or justify otherwise.
3. Equipment 48 on TJ-29,31 is 9.1A on E1 and 13.4A on A3. Coordiante, clarify, and check all affected load calculations.
4. TJ-4,6, on a 40A CB, shall have not have #10 wire, which, per NEC 240-3 (d), shall be protected at no higher than 30A.
5. Equipment 45, per NEC Table 430-148, draws 5.8A. (5.8) (120) = 696. Correct load on panel schedule.
6. I get totals of 15133, 20430, and 20853 on Phases A, B, & C of Panel TJ. Please check.
03/16/2004 DAN CASTRO ZONING REVIEW Approved
03/17/2004 MELISSA POULIN WWM REVIEW Approved