Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01199
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/15/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/15/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/15/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/15/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 03/15/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/16/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TO4CM01199 DENIED 3/16/04 1. For the fans on TJ-25,27 and TJ-33,35, (3) (1.25) =4.12. The fuse size to use is 6 per NEC 240-6. Or justify otherwise. 2. For the refrig on TJ-21,23, (9.1) (1.25) =11.4. The fuse size to use is 15 per NEC 240-6. Or justify otherwise. 3. Equipment 48 on TJ-29,31 is 9.1A on E1 and 13.4A on A3. Coordiante, clarify, and check all affected load calculations. 4. TJ-4,6, on a 40A CB, shall have not have #10 wire, which, per NEC 240-3 (d), shall be protected at no higher than 30A. 5. Equipment 45, per NEC Table 430-148, draws 5.8A. (5.8) (120) = 696. Correct load on panel schedule. 6. I get totals of 15133, 20430, and 20853 on Phases A, B, & C of Panel TJ. Please check. |
| 03/16/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 03/17/2004 | MELISSA POULIN | WWM | REVIEW | Approved |