Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM01179
Parcel: 13706132A

Address:
5433 S 12TH AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T04CM01179
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2004 Joseph Linville LANDSCAPE REVIEW Denied 1. Indicate if walls shown on the landscape plan are proposed or existing (keynote 3).

2. Revise the site and landscape plans to include loading areas and required screening. LUC 3.4.5, LUC Table 3.7.2-I. A Board of Adjustment variance application approval is required for the waiver of loading zone requirement. Add the variance case number, date of approval, variances granted and conditions imposed to the notes.

3. Include irrigation design and layout per DS 2-07.5.4.A & DS 2-07.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, controller, low-flow bubblers or drip irrigation.
07/28/2004 Loren Makus ENGINEERING REVIEW Denied DATE: July 29, 2004
TO: Arquitecto E. J. Ornelas and Associates
SUBJECT: Site Plan, El Merendero Plaza
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04CM01179

SUMMARY: The Site Plan was reviewed by Development Services Department, Engineering Division on May 13, 2004. The Site Plan was not approved at this time. Please address the following comments.

Site Plan Comments:
1) The site plan shows a proposal to widen South 12th Avenue. Show how the transition from the existing profile will be achieved. Otherwise, provide a plan showing the proposed extent of development that will be completed at this time. You may provide an additional site plan showing that the required design elements can be provided in the event that 12th Avenue is widened to its ultimate width.
2) Clearly label existing and future SVTs. The dimensions on the near side SVTs and far side SVTs are reversed.
3) Revise the solid waste container location so that they do not encroach within the utility easement.
4) Provide a letter from Environmental Services approving the use of ninety-gallon containers. The letter must specifically address the proposed pickup location.
5) Revise the North Arrow to show the correct alignment
6) The existing restaurant building is labeled with a finish floor elevation of 0.00. Provide a valid elevation.

Revise the Site Plan to address these comments and resubmit two copies for review. Include a letter explaining how each comment has been addressed.
Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services
08/12/2004 Peter McLaughlin ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Arquitecto E. J. Ornelas
100 N. Stone Ave #1002
Tucson, AZ 85701
(520) 624-8102

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T04CM01179
Retail and Wholesale Plaza
5433 S. 12th Avenue
TRANSMITTAL: August 13, 2004

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. There is overprinting of text in the area of the plan where the bicycle parking detail meets the h/c parking detail. Revise for legibility

2. Provide the maximum slope of the handicapped access aisles (adjacent to the h/c parking space) to be provided. The h/c access aisle may not be placed within the required pedestrian sidewalk. Revise location of h/c van accessible aisle and revise parking calcs if necessary. Remove the 5-foot dimension for the aisle from the h/c parking detail, as the single h/c space is required to be van accessible, with an 8-foot aisle.
ANS/ IBC

3. The location map is inaccurate. Revise to show that the 1st Avenue alignment runs along the east side of Sec. 1, T. 15 S, R 13 E. Also, Oregon and Canada Streets are not shown in their correct location. Revise to show that the subject property is in the southwest corner of the section rather than the northwest corner. Revise legal description in loc. map.
DS 2-02.2.1.A.4

4. Revise legal description in under the zoning information to be correct and complete, including all lot numbers (Lots 18 and 19).
DS 2-02.2.1.A.2

5. The bicycle parking detail does not match the configuration of the site plan relative to the building wall. Also, the calculations and keynote 14 indicate a single 2-bike rack, but the detail and plan show two 2-bike racks. Revise for consistency/clarity.
DS 2-02.2.1.A.9

6. No loading zone is shown on the site plan and it is indicated in the calculations that one is required and none are provided. A Board of Adjustment variance application approval is required for the waiver of loading zone requirement. Add the variance case number, date of approval, variances granted and conditions imposed to the notes.
DS 2-02.2.1.A.38
DS 2-02.2.1.A.14

7. Revise required MS&R building setback as follows: the MS&R setback along 12th Avenue is required to be the greater of 21 feet or height, dimensioned from back of future curb location. Revise setback table and dimension MS&R setback correctly on the drawing. The setback to adjacent R-2 zoning to the east is required to be 1-½ times the height of exterior structure wall. This setback is not met (only 4-foot buliding setback provided). The waiver of setback requirement can be rolled into the B.O.A. variance application (see comment 10).
DS 2-02.2.1.A.38
LUC 3.2.6.4
LUC 3.2.6.5

8. Provide a copy of recorded cross-access with the restaurant property to the south. Add docket and page information to the site plan for the agreement.

9. Revise north arrow to be correct.
DS 2-02.2.1.A.1

10. The maximum allowed FAR per development designator "31" is 0.90, not 0.75 as stated. Please revise.
LUC 3.2.3.2.B

11. Label the MS&R dimensions as to which one is existing and which one is future ½ right-of-way.
DS 2-02.2.1.A.19

12. Dimension the pedestrian sidewalk under the porch area to show that a minimum 4-foot clear width is provided, not counting the 2-½-foot vehicle overhang area. Show the location of any support posts which may reduce the width of pedestrian circulation. Posts or other obstructions may not reduce the width to less than four feet. DS 2-08

13. Place a note on the plan stating that the project is designed to meet the criteria of Sec. 2.8.3, MS&R setback zone. LUC 2.8.3


If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.


PMc\siteplans04\T04CM01179b
08/13/2004 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Denied See Zoning Comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/13/2004 TAMI ACHONG OUT TO CUSTOMER Completed
08/13/2004 ANGIE SHOFFSTALL REJECT SHELF Completed