Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM01170
Parcel: 121083000

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM01170
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2004 JIM EGAN FIRE REVIEW Approved
03/16/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/16/2004 ROBERT SHERRY WATER REVIEW Approved
03/16/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/17/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
03/18/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
03/18/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
04/20/2004 GERRY KOZIOL WWM REVIEW Approved
04/20/2004 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review