Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM01111
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/09/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. An indirect waste receptor (floor sink) may not be installed in a toilet room or closet. Reference Section 804.1, UPC 1994. 2. Show that the water heater complies with Section 511.2, UPC 1994 for access and working space. 3. Provide cleanout for P4. Reference Section 707.4, UPC 1994. |
03/09/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/09/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
03/16/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
03/16/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/16/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
03/17/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
03/17/2004 | LLESNY1 | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
03/17/2004 | JIM EGAN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/17/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |