Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T04CM01109
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/30/2004 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: DESA, Inc. DATE: March 30, 2004 35 N. Tucson Blvd. Tucson, Arizona 85716 SUBJECT: 5561 E. Speedway Blvd Site plan T04CM01109 (First Review) T14S, R14E, Section 01 RESUBMITTAL REQUIRED: Site Plan and Drainage Statement. The Site Plan (SP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Site Plan: 1. Please include a response letter to the comments along with the corrected copies of the SP. 2. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16. 3. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The previous permit has expired therefore a new agreement/approval with Environmental Services will be required. Please contact John Clark at 791-7983 for more information. 4. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. 5. Please show handicap ramps at the new ingress/egress on Speedway Blvd. 6. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice. 7. Add note: "Depress all landscaped areas 6" maximum for water harvesting". Drainage Statement: 1. A Drainage Statement is required for parcels not affected by 100 year flows of 100 cfs, of more⦠per S.M.D.D.F.M., chap. II, 2.1.3. 2. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.1.3. 3. Show the project address on the cover of the Drainage Statement. If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1193 office (520) 879-8010 fax |
| 04/01/2004 | David Rivera | ZONING | REVIEW | Approved | |
| 04/01/2004 | David Rivera | HANDICAP-SITE | REVIEW | Approved | |
| 04/05/2004 | Andrew Connor | NPPO | REVIEW | Approved | |
| 04/05/2004 | Andrew Connor | LANDSCAPE | REVIEW | Denied | 1) Landscape plan shall include irrigation specification design and layout per DS 2-07.5.4.A & DS 2-07.5.4.B included sleeves for driveways and sidewalks, locations of valves, controller, and low-flow bubblers or drip irrigation. 2) Indicate methods by which water harvesting or storm water runoff is used to benefit all planting areas on the site per DS 2-07.2.2.B.6 3) Indicate on landscape plan DG between landscape buffer and sidewalk along E. Speedway Blvd per LUC 3.7.2.7 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/06/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 04/06/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |