Permit Number: T04CM01044
Parcel: 123150560

Address:
920 E ELM ST #02

Review Status: Completed

Review Details: 3RD PARTY REVIEW-RESIDENTIAL

Permit Number - T04CM01044
Review Name: 3RD PARTY REVIEW-RESIDENTIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2004 TACHONG1 WWM REVIEW Needs Review
04/09/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied Plans submitted for building permit have been checked for conformance with current codes. Corrections required are noted below. All corrections must be made to the original drawings and two new complete and corrected sets resubmitted along with a written reply to all comments. To facilitate a timely recheck please insure all drawing changes or revisions made to previously issued sheets are highlighted by cloud and revision number.

ARCHITECTURAL COMMENTS
Sheet 1.0
1. Show the location of the electrical service. Specify overhead drop or underground cable. The electrical plan states an underground cable is scheduled.

Sheet 2.0
1. Provide building permit information for the existing bedroom #3. This appears to be a building code violation.

2. Reference detail 7/6.0 for the fire resistive wall. Ref. R321.

3. Clarify the overall dimension in the north south direction. Dimensions of 46’-4” and 45’-0” are shown.

4. Specify provisions for penetrations of the fire resistive common wall. Ref. R321.3.

5. Show the location of the attic access. Ref. R807.

Sheet 3.0
1. Provide attic ventilation calculations. Ref. R806.

Sheet 4.0
1. Show where the edge of slab detail 4/4.0 occurs on the plan.

2. Revise the minimum footing widths for conventional light frame construction. Ref. Table R403.1.

3. Specify / detail the connection at the post to foundation condition at the covered patio.

Sheet 5.0
1. In framing plan B/5.0, show the header size at the opening to the existing residence.

2. Specify the post to beam connection at the covered patio.

Sheet 6.0
1. In detail 2/6.0, the riser and tread dimensions are not consistent with the floor plan. Resolve the discrepancy.

STRUCTURAL COMMENTS
General
1. Coordinate the load bearing condition at the east great room wall. Trusses marked 501 and 502 are 3 point bearing trusses.

2. Show or note on the framing plan the double trusses marked T01.

3. Account for the concentrated mechanical equipment loads in the truss design. Ref. R802.10.1.4. Show the location of the roof mounted mechanical equipment on the plan for each dwelling.

PLUMBING COMMENTS
Sheet 7.0
1. Show the fixture unit values as given in UPC Table 6-3.

2. Water note 5 specifies condensate disposal at plumbing vent. This method of indirect waste disposal is not permitted. Show condensate routing to an approved point of termination. Ref. UPC 801.

3. Specify pressure balance or thermostatic mixing valves per UPC Table 7-5.

4. Show the 3” waste down to the lower level.


MECHANICAL COMMENTS
Sheet 8.0
1. Provide a specification for the exhaust fans.

2. Show the range hood vent size and termination. Ref. M1502.

ELECTRICAL COMMENTS
Sheet 9.0
1. The bath 2 in unit 1 shows an existing receptacle in a portion of the project that has not been constructed.

ENERGY COMMENTS – The energy portion has been reviewed and approved.

Should you have any inquires regarding this letter, please do not hesitate to contact the Plans Examiner at (520) 791-2007 or the Building Official at (520) 791-5550.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/09/2004 TAMI ACHONG OUT TO CUSTOMER Completed