Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM01011 4/11/06

1. Do not accept Owner-supplied Track and Lights. Please have the Owner make the selection, then document by catalogue cut sheets and catalogue number on plans, and have Registrant seal, sign and date the documentation as such to ensure compliance with the Lighting Code.
2. It appears that "K2-1,3,7" on the Power Plan should read "P-1,3,7."
3. Please note that the voltage is 208, not 240. Correct Panel P load calculation.
4. Please cut the plotted plans to standard size.