Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T04CM01011
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM01011 4/11/06 1. Do not accept Owner-supplied Track and Lights. Please have the Owner make the selection, then document by catalogue cut sheets and catalogue number on plans, and have Registrant seal, sign and date the documentation as such to ensure compliance with the Lighting Code. 2. It appears that "K2-1,3,7" on the Power Plan should read "P-1,3,7." 3. Please note that the voltage is 208, not 240. Correct Panel P load calculation. 4. Please cut the plotted plans to standard size. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/17/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 04/17/2006 | SUE REEVES | REJECT SHELF | Completed |