Permit Number: T04CM00946
Parcel: 115181120

Address:
1126 N 13TH AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM00946
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2004 Neil Saunders BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T04CM00946

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.
3. Water heater compartment has been deemed in violation of the 3' setback by our Zoning department. Options: Move the water heater to backside of house. Apply for an LDO and fire rate the shed. Regardless of which option, shed must be described in more detail.
4. Scale is incorrect on pages A3.1, e2.1 and M2.1.

Site Plan

1. Note 5 is missing.
2. Show sewer line on property and where it enters the building.

Floor Plan

1. Note 2, "new 6' site wall". See site plan for locations of note and clarify.
2. Note 6 is missing.
3. Clarify note 14 and 17, "not used". They are shown on plan.
4. Callout window size in shower. Glass in shower must be tempered if the lower edge of the bottom pane is within 60" of standing surface per R308.4.
5. Note that bathtub and shower enclosures shall be finished per p2710 with ceramic tile, or a listed enclosure, to height of 72" above the drain.
6. Note and specify that shower enclosures shall have a minimum finished interior of 1024 square inches and shall be capable of encompassing a minimum 30" circle per UPC sec 410. All glass enclosures shall be tempered.

Structural Plan

1. Middle wall behind new washer space is smaller than the original wall. Was this wall a bearing wall? If so, show how the wall will continue to support the roof/ceiling assembly.

Plumbing Plan

1. Show T & P line at water heater.
2. Note on plans compliance with water conservation; Water closets 1.6 gallons per flush, sinks and showerheads 3 gallons per minute.
3. Note on plans that shower and Tub/shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
4. The City of Tucson has not adopted the plumbing section of the IRC 2000. The current code being used is the 1994 UPC with state amendments. All plans must reference this code.

Mechanical Plans

1. Provide a vent for the dryer.
2. Is air handler in the attic or on the roof? If in the attic provide attic access, working platform, a switched light and a nearby receptacle per M1305.1.3.
3. Show exhaust fan in bathroom in lieu of an operable window per R303.3.

Electrical Plans

1. Note on plans: Electrical work shall comply with chapters 33-42, 2000 IRC.
2. Smoke detector required in closet per R317. Note that smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup.
3. Bathroom receptacle to be on a dedicated 20 amp circuit with no other outlets (i.e. lights, fan) per E3603.4.
4. Peninsula counter tops shall have at least one receptacle at each counter space with a long dimension of 24" or greater per E3801.4.2 and E3802.4.3. Provide a receptacle at both countertops adjacent bathroom door.
5. Show switch for disposal.
6. Dishwasher and disposal can be on same circuit (12).
7. Two 20 amp small appliance circuits shall be installed to serve the kitchen countertops. (18 and 14).
8. Provide receptacles on both sides of the shared wall between the bedroom and the living room. Reference E3801.2.1 and E3801.2.2.
9. Indicate grounding and bonding methods. (i.e. ground rods, distance between rods, size wire, etc).
10. Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used.

ANY QUESTIONS, CONTACT NEIL SAUNDERS @ 791-5550 x2208
03/22/2004 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/25/2004 TAMI ACHONG OUT TO CUSTOMER Completed
03/23/2004 SUE REEVES REJECT SHELF Completed