Permit Number: T04CM00939
Parcel: 110103030

Address:
3182 N SWAN RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T04CM00939
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2004 TACHONG1 WWM REVIEW Needs Review
03/16/2004 TACHONG1 ZONING REVIEW Needs Review
03/16/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied Plans submitted for building permit have been checked for conformance with current codes. Corrections required are noted below. All corrections must be made to the original drawings and two new complete and corrected sets resubmitted along with a written reply to all comments. To facilitate a timely recheck please insure all drawing changes or revisions made to previously issued sheets are highlighted by cloud and revision number.

ARCHITECTURAL COMMENTS
Sheet TS
1. Please clarify the occupant load for room 103. Ref. IBC 1003.2.2.2. Coordinate exits and exit widths. Ref. IBC 1003.2.3, 1004.

Sheet A1
1. Show provisions for meeting the minimum plumbing fixture requirements. Ref. IBC 2902.1.

2. Show the attic access and provide a detail. Ref. IBC 1208.

3. Clarify provisions for attic ventilation. Ref. IBC 1202.

Sheet A3
1. The structural sheet referenced in detail 7/A3 is not a part of the plans. Please clarify and specify horizontal joint reinforcement at 16” on center.

Sheet A4
1. Keynote 15.4 is not shown on the plan. Please show the location(s) where this occurs.

Sheet A5
1. Dimension the countertop height of the common use breakroom counter to comply with ANSI A117.1 903.

2. Keynote 15.3 conflicts with mechanical equipment schedule on Sheet M2. Please revise to reference the operating weights shown in the mechanical specifications.

Sheet A8
1. Delete the reference to the future ceiling. The ceiling is a part of this permit.


STRUCTURAL COMMENTS – The structural portion has been reviewed and approved.


PLUMBING COMMENTS
Sheet P1
1. Room 112 shows a callout for ¾” condensate above ceiling. There is not a ¾” condensate line here. Please delete.

2. Show the reduced pressure valve on the water service. Ref. UPC 608.2.

Sheet P2
1. Specify provisions for access to water heater mounted above the 9”-6” ceiling in room 109 or mount below 8’-0”. Ref. UPC 511.


MECHANICAL COMMENTS
Sheet M1
1. Plan notes at heat pump 3 indicate smoke detector installation as typical. Please clarify if all units are scheduled for smoke detection systems. Ref. IMC 606.


ELECTRICAL COMMENTS
Sheet E1
1. Heat pump 2 circuits have a labeling error. This should show “B”-37-39-41.

Sheet E3
1. Please revise the smoke detector detail to show the detectors in the return air. Ref. IMC 606.


ENERGY COMMENTS – The energy portion has been reviewed and approved.


Should you have any inquires regarding this letter, please do not hesitate to contact the Plans Examiner at (520) 791-2007 or the Building Official at (520) 791-5550.
03/16/2004 TACHONG1 WATER REVIEW Needs Review
03/16/2004 TACHONG1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2004 TAMI ACHONG OUT TO CUSTOMER Completed