Permit Number: T04CM00933
Parcel: 11615087J

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00933
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/03/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/03/2004 ROBERT SHERRY WATER REVIEW Approved
03/09/2004 JIM EGAN FIRE REVIEW Approved
03/12/2004 DOUG WILLIAMS ENGINEERING REVIEW Denied A Floodplain Use Permit is required prior to approval.
03/16/2004 MARTIN HAEBERLE ELECTRICAL-COMMERCIAL REVIEW Passed
03/16/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Provide exit plan and width calculations for revised exit path of corridor.
2. Show how independent egress is being achieved per section 407.4.2 IBC
3. Provide details for proposed walls.
03/29/2004 GERRY KOZIOL WWM REVIEW Completed