Permit Number: T04CM00931
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00931
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/04/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide details for the penetrations of the fire-rated floor.
03/04/2004 ROBERT SHERRY WATER REVIEW Approved
03/09/2004 JIM EGAN FIRE REVIEW Approved
03/15/2004 MARTIN HAEBERLE ELECTRICAL-COMMERCIAL REVIEW Passed
03/15/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Indicate listing used and method of anchoring of drywall. Reference Sheet 6.2 Detail A.
2. Special Inspection required for epoxy bolts, expansion bolts, and welding. Include inspection reports.
3. Provide structural calculations indicating existing and proposed loads on structural members are within design parameters. Note: include seismic calculations and utilize importance factor for essential facilities.
4. Fire stop systems used to be incorporated into plans. Include protection of new structural members and patches.
5. Indicate location of fire dampers and typ
03/26/2004 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/27/2004 LISA LESNY OUT TO CUSTOMER Completed
03/27/2004 ANGIE SHOFFSTALL REJECT SHELF Completed