Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00931
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/04/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
03/04/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide details for the penetrations of the fire-rated floor. |
03/04/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/09/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
03/15/2004 | MARTIN HAEBERLE | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
03/15/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Indicate listing used and method of anchoring of drywall. Reference Sheet 6.2 Detail A. 2. Special Inspection required for epoxy bolts, expansion bolts, and welding. Include inspection reports. 3. Provide structural calculations indicating existing and proposed loads on structural members are within design parameters. Note: include seismic calculations and utilize importance factor for essential facilities. 4. Fire stop systems used to be incorporated into plans. Include protection of new structural members and patches. 5. Indicate location of fire dampers and typ |
03/26/2004 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/27/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |
03/27/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |