Permit Number: T04CM00930
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Stopped

Review Details: COMMERCIAL TI

Permit Number - T04CM00930
Review Name: COMMERCIAL TI
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/04/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/04/2004 ROBERT SHERRY WATER REVIEW Approved
03/08/2004 JIM EGAN FIRE REVIEW Approved
03/08/2004 MARTIN HAEBERLE ELECTRICAL-COMMERCIAL REVIEW Passed
03/08/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Provide listed fire stop system details on plans. Please include all fire stop penetration systems to be used.
2. Plans to reflect foundation for equipment reflected in structural calculations.
3. Show on plans detail for equipment attachment to ceiling floor assembly. Include how 2-hour fire assembly is to be maintained.
03/09/2004 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2004 SUE REEVES REJECT SHELF Stop
03/02/2004 ANY OUT TO CUSTOMER Stopped