Permit Review Detail
Review Status: Stopped
Review Details: COMMERCIAL TI
Permit Number - T04CM00930
Review Name: COMMERCIAL TI
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/04/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/04/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/08/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/08/2004 | MARTIN HAEBERLE | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 03/08/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide listed fire stop system details on plans. Please include all fire stop penetration systems to be used. 2. Plans to reflect foundation for equipment reflected in structural calculations. 3. Show on plans detail for equipment attachment to ceiling floor assembly. Include how 2-hour fire assembly is to be maintained. |
| 03/09/2004 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/09/2004 | SUE REEVES | REJECT SHELF | Stop |
| 03/02/2004 | ANY | OUT TO CUSTOMER | Stopped |