Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL
Permit Number - T04CM00835
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2004 | DHERRON1 | WWM | REVIEW | Needs Review | |
| 03/11/2004 | GP | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Denied | Plans submitted for building permit have been checked for conformance with current codes. Corrections required are noted below. All corrections must be made to the original drawings and two new complete and corrected sets resubmitted along with a written reply to all comments. To facilitate a timely recheck please insure all drawing changes or revisions made to previously issued sheets are highlighted by cloud and revision number. ARCHITECTURAL COMMENTS Sheet A1 1. Please show access to concealed attic spaces. Ref. IBC 1208. 2. The window in room 113, within a 24" arc swing of door 114, requires safety glazing. Ref. IBC 2406.2.6. 3. Provide the listing number from an approved testing agency for wall type 6A. This assembly appears to be the GA file no.3910. Please clarify. Sheet A3 1. Please provide a construction dimension for window sill heights. Sheet A4 1. Complete the ceiling type keynote reference in section A/A9 for rooms 205, 203, 104, 114 and 112. Sheet A5 1. Doors 106 and 116 encroach into the path of egress. Please address. Ref. IBC 1003.2.3.1. 2. Show wall types 7B and 7C in rooms 102, 108, 207 and 204. 3. Note exterior wall types as 7A unless noted otherwise. 4. No landing is shown for door 207B. Please clarify. Ref. IBC 1003.3.1.4. Sheet A7 1. In detail 7/A7 specify maximum threshold bevel of 50%. Ref. IBC 1003.3.1.6. Sheet A9 1. Specify the listing number from an approved testing agency for the rated assembly shown in detail 5/A9. STRUCTURAL COMMENTS - The structural portion has been reviewed and approved. PLUMBING COMMENTS General 1. The 1/8" scale is too small to clearly show the work to be performed. Sheets P1 and P2 1. Show supply, soil and vent lines to fixture P3 in details 9/P2 and 8/P2. 2. Show all fixtures in details 1/P2, 2/P2, 3/P2 and 4/P2. Only nine points of supply are shown, where 13 are to be installed. Only eight points of connection to soil and vent are shown, where 14 are to be installed. Sheet P2 1. Show all required cleanouts on the isometric drawings. Ref. UPC 707.4. 2. Dimension the mounting height of the water heaters. Detail provisions for access if mounting is greater than 8'-0" above the finished floor. Ref. UPC 511. Sheet P4 1. Include the hose bibb and pressure reducing valve quantities in the fixture schedule. MECHANICAL COMMENTS General 1. The 1/8" scale is too small to clearly show the work to be performed. Sheet M1 1. Show smoke detection system control for HP-1 and HP-2. Ref. IMC 606. Coordinate with electrical. ELECTRICAL COMMENTS General 1. Coordinate smoke detection system control with the mechanical plan. Ref. IMC 606. ENERGY COMMENTS - The energy portion has been reviewed and approved. Should you have any inquires regarding this letter, please do not hesitate to contact the Plans Examiner at (520) 791-2007 or the Building Official at (520) 791-5550. DAVE MANN, P.E. BUILDING OFFICIAL BY:_____________________ Joe Zeman Plans Examiner |
| 03/11/2004 | DHERRON1 | WATER | REVIEW | Needs Review | |
| 03/11/2004 | DHERRON1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/11/2004 | DHERRON1 | OUT TO CUSTOMER | Completed |