Review Details: COMMERCIAL TI

Permit Number - T04CM00766
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2004 ANY BUILDING-COMMERCIAL REVIEW Denied S1. SEE COMMENTS ON SUITE #120, T04CM00733.
02/19/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the drawings to clearly show the proposed work.
2. Justify the sizes of the water piping shown on sheet A-1.
02/19/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/23/2004 JIM EGAN FIRE REVIEW Approved
02/23/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/23/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM00766 DENIED 2/19/04
1. Clarify the term "split lighting fixture."
2. Provide a disconnect for the Insta-Hot per NEC 422.
3. Provide panel and circuit numbers for all new equipment.
02/24/2004 EGRANT1 WATER REVIEW Approved
02/24/2004 PETER MCLAUGHLIN ZONING REVIEW Approved