Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00741
Parcel: 11304161B

Address:
720 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00741
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2004 JIM EGAN FIRE REVIEW Approved
03/18/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/18/2004 DAN CASTRO ZONING REVIEW Approved
03/18/2004 ROBERT SHERRY WATER REVIEW Approved
03/18/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/19/2004 ANY BUILDING-COMMERCIAL REVIEW Approved
03/19/2004 EGRANT1 WWM REVIEW Passed
03/19/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
03/19/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM00741 DENIED 3/18/04

1. Sizing of Main Bonding Jumper shall be per NEC Table 250-66. If the Service Entrance Conductors are 350 MCM AL, then the MBJ shall be #2. Please add the following note: "Size MBJ at #2".
2. Please see Comments 8 & 9 from the previous review. The exception cited in the response does not apply, because the circuit going to the Tanning Building is a Feeder, not a Branch Circuit. See Article 100 for "definitions".

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2004 EGRANT1 OUT TO CUSTOMER Completed