Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00741
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/18/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/18/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 03/18/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/18/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/19/2004 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/19/2004 | EGRANT1 | WWM | REVIEW | Passed | |
| 03/19/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 03/19/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM00741 DENIED 3/18/04 1. Sizing of Main Bonding Jumper shall be per NEC Table 250-66. If the Service Entrance Conductors are 350 MCM AL, then the MBJ shall be #2. Please add the following note: "Size MBJ at #2". 2. Please see Comments 8 & 9 from the previous review. The exception cited in the response does not apply, because the circuit going to the Tanning Building is a Feeder, not a Branch Circuit. See Article 100 for "definitions". |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/19/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |