Permit Number: T04CM00716
Parcel: 12709007J

Review Status: Completed

Review Details: SITE

Permit Number - T04CM00716
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2004 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Indicate project address on Sheet 2 and 3. D.S. 2-02.2.1.A.3

2. Indicate location map on Sheet 2 and 3. D.S. 2-02.2.1.A.4

3. Indicate all existing buildings and structures, including roof slope and location of downspouts. D.S. 2-02.2.1.A.6 NOTE: All roof spouts will be routed under any adjacent sidewalk. Sidewalks shall be flood free for all storm discharges of up to a ten (10) year flood event. Indicate roof direction/drainage. D.S. 2-08.3.1 & 4.1.E

4. Indicate drainage patterns, proposed finish floor elevation(s) and finish grades. Do not obstruct offsite to onsite flows. D.S. 2-02.2.1.A.16

5. Indicate if street is Public or Private. Street ? is a MS&R with Future R.O.W. of ? which intersects with ? , requiring a widening of ? Alley access is not allowed. Align driveway access to existing driveway across the street. Closed unused driveways. Show adjacent driveways. Show existing road medians. D.S. 2-02.2.1.A.18

6. Indicate recording docket and page reference for easement. D.S. 2-02.2.1.A.20

7. The standard dimensions for a refuse enclosure interior is 10' x 10'. Sheet 1, Detail Trash Enclosure indicates interior dimensions to be 12' x 11', which is acceptable.

8. Indicate activity number T04CM00716 on Sheets 1 to 5. Indicate activity number T04BU00344 to Sheets 3 to 5.

9. The spot grades in the pedestrian pathway indicate ponding. Indicate direction of drainage flow.
03/08/2004 JIM EGAN FIRE REVIEW Approved
03/11/2004 JOE LINVILLE NPPO REVIEW Approved
03/11/2004 Joseph Linville LANDSCAPE REVIEW Approved
03/15/2004 Daniel Castro HANDICAP-SITE REVIEW Approved
03/15/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next
Submittal, which states how all Zoning Review Section comments Regarding the Land Use Code and Development Standards were Addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. Verify the site address. County records indicate 5855 E. Broadway is located west of the subject property. (D.S. 2-02.2.1.A.3)

2. Revise the vehicle parking calculation as follows: a) Building 2 may be parked at 1 space per 400 square feet GFA (Furniture Retail), therefore requiring 28 vehicle parking spaces for the proposed 11,223 S.F. building. b) Building 3 must be parked at 1 space per 200 square feet GFA. The mezzanine/receiving area is ancillary to the principal use "retail". (D.S. 2-02.2.1.A.8) (D.S. 2-02.2.2.A.4)

3. How is vehicular and pedestrian cross access provided to Parcel 1?

4. If applicable, provide the location, type, size, and height of existing and proposed signage and outdoor lighting on the site plan. (D.S. 2-02.2.1.A.13) (D.S. 2-02.2.1.A.25)

5. All existing or proposed easements and abandoned easements must be shown on the plan including width, type, and recording docket and page reference. (D.S. 2-02.2.1.A.20)

6. Note the percentage of building area expansion. (D.S. 2-02.2.1.A.6)

7. All requested changes must be made to the site and landscape plans.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2004 TAMI ACHONG OUT TO CUSTOMER Completed
03/15/2004 SUE REEVES REJECT SHELF Completed