Permit Number: T04CM00714
Parcel: 115020400

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T04CM00714
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied Plans submitted for building permit have been checked for conformance with current codes. Corrections required are noted below. All corrections must be made to the original drawings and two new complete and corrected sets resubmitted along with a written reply to all comments. To facilitate a timely recheck please insure all drawing changes or revisions made to previously issued sheets are highlighted by cloud and revision number.

ARCHITECTURAL COMMENTS
Sheet 1.0
1. Provide a dimension for the existing hcs.

2. Note the size of the water meter.

3. Provide tread and riser dimensions, landing dimensions and note handrail provisions to comply with R312, 314 and 315.

Sheet 3.0
1. Provide a detail of the porch footings.

STRUCTURAL COMMENTS
General
1. Include the engineered truss design, prepared by an Arizona P. E. with the second submittal.

Sheet 5.0
1. Provide a detail of the post to beam connection at the exterior porch.

PLUMBING COMMENTS
Sheet 6.0
1. The fixture unit schedule shows 2 washing machines. Only one clothes washer is shown on the plan. Clarify.

2. Show fixture unit values consistent with the Uniform Plumbing Code.

3. Include the water supply calculation.

MECHANICAL COMMENTS
1. Condensate drain may not terminate at plumbing vents. Specify an approve point of termination.

ELECTRICAL COMMENTS
Sheet 7.0
1. Circuits 22 and 24 were not shown on the plan. Clarify.

ENERGY COMMENTS - The energy portion has been reviewed and approved.

Should you have any inquires regarding this letter, please do not hesitate to contact the Plans Examiner at (520) 791-2007 or the Building Official at (520) 791-5550.
03/02/2004 DHERRON1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/02/2004 DHERRON1 OUT TO CUSTOMER Completed