Permit Number: T04CM00705
Parcel: 117090400

Address:
1015 S 7TH AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM00705
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2004 GERRY KOZIOL WWM REVIEW Denied Needs WW 8th floor credit evaluation.
06/14/2004 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM00705

6/15/04 1015 S. 7TH AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FLOOR PLANS:

1. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

STRUCTURAL PLANS:

1. PLEASE JUSTIFY THE CEILING JOIST'S ABILITY TO MAKE THEIR SPANS. THEY APPEAR TO EXCEED THE SPANS IN TABLE R802.4(2) FOR THE SPECIFIED #2 H.F. AND FOR #2 D.F.

2. HOW DO THE RAFTERS @ 24" O.C. AND THE CEILING JOISTS @ 16" O.C. COMPLY WITH R802.3.1?

SECTIONS - DETAILS - MISC. NOTES:

1. 3 / 4 ; PLEASE DESCRIBE THE INTERIOR FINISH.

2. 1 / 5 ; DIMENSION AND DESCRIBE THE RAFTER TAIL TO RAFTER CONNECTION.

3. LINTEL SCHEDULE / 5 ; TABLE R611.7(3) REQUIRES THE SPACING OF THE STIRRUPS TO BE HALF THE DEPTH OF THE LINTEL. PLEASE JUSTIFY THE 16" STIRRUP SPACING.

PLUMBING PLANS:

1. PLUMBING NOTE #8 / 6 ; THE CONDENSATE IS NOT TO DRAIN IN A VENT (WET VENT). A TRAP'S TAIL PIECE OR OVER THE ROOF'S EDGE ARE OKAY.

MECHANICAL PLANS:

1. PLEASE CONFIRM THE BLOWER UNIT, APPEARS TO BE 2 TON, IS COMPATIBLE WITH THE 4 TON HEAT PUMP.


ELECTRICAL PLANS:

1. PLEASE NOTE THAT LIGHT FIXTURES IN SHOWERS ARE REQUIRED TO BE LISTED AS APPROVED FOR USE IN WET AREAS.

2. PROVIDE A RECEPTACLE FOR THE WALL WITHIN 6' OF THE NORTH BEDROOM DOOR. SEE E3801.2.1 .

3. PROVIDE A RECEPTACLE IN THE DINING ROON BETWEEN THE PORCH AND KITCHEN DOORS. SEE E3801.2.2 , ITEM 1 .



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
06/16/2004 TAMI ACHONG OUT TO CUSTOMER Completed
06/16/2004 SUE REEVES REJECT SHELF Completed