Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2004 MELISSA POULIN WWM REVIEW Approved
05/10/2004 Christy Foreman BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS PROJECT #T04CM00682
5/11/04 3307 E. Elida St


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.
SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical codes. All code references are to the 2000 IRC and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
1. Note that the current residential building code adopted by the City of Tucson is the 2000 IRC. All references to the building code are 2000 IRC unless noted otherwise.
2. All plans shall be legible and a scale no smaller than ¼ inch = 1-foot shall be used for all floor plans, framing plans and elevations. Details and cross sections shall be a minimum 3/8 inch = 1-foot scale.
3. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints.
4. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
5. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.
SITE PLAN: (NOT REQUIRED FOR MODEL PLANS)
1. Provide a site plan indicating the location of all structures on the property. Note 1 hour fire wall seperation.
FOUNDATION PLANS:
1 Locate and specify all anchor-bolt spacing on the foundation plan. Minimum ½" diameter with 7" embedment into concrete or masonry. Maximum spacing 6' O.C. and within 12" of each end of sill plate per R403.1.6.
2. All foundation hold-downs and anchor-bolt spacing for brace walls shall be specified and located.
FLOOR PLANS:
1. Note that bathtub and shower enclosures shall be finished per P2710 with ceramic tile, or a listed enclosure, to a height of 72" above the drain per R702.4 and R307.2.
STRUCTURAL PLANS:
1. Detail all brace wall connections from the foundation to the roof plywood.
2. Provide brace wall details and notes for exterior frame walls and main cross-stud partitions, or use fully braced, per R602.10.3. A minimum panel width of 48" is required to effectively brace the partition. See table R602.10.3, category "C". If bracing does not comply, provide a lateral analysis or alternate design to be reviewed by the plan examiner. Wind forces for single story residences shall use 90 MPH, exposure "B". Two story residences or areas of higher wind shall use exposure "C".
3. Specify weight of roof system items (for example, weight of selected tile). Provide ICBO evaluation report number and manufacturer of all concrete or clay-type roofing.
ELEVATIONS:
1. Note and specify all roof slopes appropriate to material. (minimum allowable roof slope is ¼" per foot per R905)
2. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply.
SECTIONS - DETAILS - MISC. NOTES:
1. Note and specify the spacing anchor bolts for sill plates.
PLUMBING PLANS:
1. Water line: Provide the total fixture unit demand and maximum developed length.
2. Note on plan compliance with the water conservation requirements. Water closets, 1.6 gallons per flush, sinks and shower heads, 3 gallons per minute.
3. Note on plans that shower and tub / shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
MECHANICAL PLANS:
1. Show exhaust fan locations for bathrooms, water closet compartments and similar rooms in lieu of operable windows, per R303.3.
ELECTRICAL PLANS:
1. Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used, per E4001.6.
2. Submit panel schedule showing circuit wire size. Also show feeder size and ground for sub-panel feed.
If you have any questions, please contact your assigned plans examiner Christy Foreman at 791-5550, extension 1113.

NOTE: As of 2-02-01 the City of Tucson has adopted the 2000 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code. All model plans shall reference these codes.