Permit Number: T04CM00658
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00658
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 04/28/04

1) Deferred submittals shall have prior approval from the building official. Provide a letter
to request approval of the deferred submittal(s). Section 106.3.4.2
2) Regarding sprayed fire resistence to steel colmuns and beams. Determine the thickness
of protection on those elements as specified in sections 720.5.1.3,720.5.2.1, and 720.5.2.3.
05/03/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide detail showing how the hydronic and other piping is to be supported from the structure (i.e. the connection to the building structure).
05/03/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate detail 9/M8.1 with the water piping floor plan (the reduced pressure backflow preventers in room 323).
2. Provide manufacturer and model number for the "in-line vacuum breaker" and show how it is to be installed.
05/06/2004 ASHOFFS1 ZONING REVIEW Needs Review
05/06/2004 ASHOFFS1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2004 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed