Permit Number: T04CM00609
Parcel: 121110220

Review Status: Completed

Review Details: SITE

Permit Number - T04CM00609
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2004 Blanca Espino ENGINEERING REVIEW Denied Site Plan
1. Sheet C-1.1 indicates two legal property descriptions with two different lot dimensions and bearings. A Lot Combination is required. D.S. 2-02.2.1.A.2

2. Indicate proposed building, including roof slope and location of downspouts D.S. 2-02.2.1.A.6 All roof spouts will be routed under any adjacent sidewalk. Sidewalks shall be flood free for all storm discharges of up to a 10- year flood event. D.S. 2-08.3.1

3. Delineate limits of the 100-year floodplain and water surface elevation on Site Plan. D.S. 2-02.2.1.A.15

4. Indicate drainage flow on proposed pavement. D.S. 2-02.2.1.A.16

5. If applicable, indicate all easements of record to be graphically shown on the plan together with recording docket and page reference. D.S. 2-02.2.1.A.20

6. Indicate existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number on Site Plan. D.S. 2-02.2.1.A.23

7. Dumpster is not accessible. Demonstrate vehicle maneuverability fully dimensioned. D.S.6-01.10.Figure 1 Be aware vehicles require 36' inside radius and 50' outside radius. Sanitation vehicles should not be required to back up more than 50'. Indicate a refuse enclosure detail as per D.S. 6-01.4.2
03/16/2004 JOE LINVILLE NPPO REVIEW Denied Submit documentation per DS 2-15.2.0 with the application for exception. Aerial photos of the site indicate the existence of vegetation.
03/16/2004 JOE LINVILLE LANDSCAPE REVIEW Denied Submit a copy of the site and landscape plans in effect the last time the site received zoning compliance approval.

Submit a landscape plan which includes the content specified in DS 2-07.0

Revise the site/landscape plans to include provisions for dust control per LUC 3.7.2.7.

Submit a copy of BOA decision letter and any relevant plans.
03/17/2004 David Rivera HANDICAP-SITE REVIEW Denied see zoning review commnets
03/17/2004 David Rivera ZONING REVIEW Denied DSC TRANSMITTAL

FROM: David Rivera Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT: T04CM00609
Wireless Switching Center - Utility use
4927 E. Speedway Boulevard
Site Plan

Transmittal date: 1st Review March 17, 2004

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The property description as listed does not match the Assessor's record information. As a matter of fact this development encompasses two separate parcels with separate Pima County Tax Code Parcel Numbers. Prior to final approval of thus site plan, a Tax Code Parcel number combo and a recorded Lot Combo Covenant that will run with the land will be required. The tax code combo must be processed through the Pima County Assessor's office. Please call their office for information regarding the required documentation and process. The lot combo covenant form may de downloaded from the City of Tucson Development Service web site. If you have any questions regarding this comment or have problems downloading the lot combo covenant form, feel free to call me at 791-5608 ext. 1181. Keep in mind that the legal description must be revised on the site plan to clearly describe the entire parcel. DS 2-02.2.1.A.2

2. The location map must cover a one square mile area and must be drawn at a scale of 3 inches = 1 mile. The section, township and range and scale of the map are to be listed below the location map. DS 2-02.2.1.A.4

3. Label the building dimensions for the proposed prefab structure. DS 2-02.2.1.A.6

4. The number of vehicle parking spaces that are required for this use is 11. Per the site plan 14 useable spaces are shown. Revise the vehicle parking calculations to state that 11 vehicle-parking spaces are required and that 14 have been provided. Also please dimension the parking spaces that face Speedway. DS 2-02.2.1.A.8

5. Dimension the driveway entrance and the PAAL between the two rows of parking. The PAAL between the proposed loading zone and the east property line must be dimensioned. The minimum width for two-way traffic is 24 feet. Also the gate granting access to the back yard area must be a 24 feet wide and must be relocated to the east property line away from the back of the loading zone. DS 2-02.2.1.A.11

6. List the proposed use of the new structure, storage area, mechanical room, office etc. The pedestrian circulation must connect from the existing onsite sidewalk to the new building. A minimum four-foot wide concrete sidewalk is required. If the sidewalk is placed next to the PAAL the sidewalk must be physically separated by curbing, bollards, raised sidewalk etc. The sidewalk must also be accessible for the handicapped. Show ramps where required. DS 2-02.2.1.A.12

7. Indicate the location, type, and size of existing or proposed freestanding signage or billboards. DS 2-02.2.1.A.13

8. As stated in comment 5, the loading zone location may not be placed within a PAAL area. Based on the location of the gates leading to the back yard the vehicles needing access to the back yard would have to cross over the loading zone. The gates must be relocated and made 24 feet wide or the loading zone must be placed elsewhere and maneuverability into and out of the loading zone must be demonstrated. DS 2-02.2.1.A.14

9. If applicable show and label the location, type, and height of existing or proposed freestanding lighting. DS 2-02.2.1.A.27

10. See landscape reviewer comments regarding the requirements for landscape borders and screening. DS 2-02.2.1.A.27

11. Label the zoning classifications adjacent to this site including the zoning classification across the street. DS 2-02.2.1.A.28

12. Under the Use note add the following, (Distribution System DD "12" Subject to LUC 3.5.11.1.A., .E and .I) DS 2-02.2.1.A.31

13. The refuse container may have to be relocated if the issue with the loading and PAAL cannot be resolved. See Engineering comments for more information regarding the refuse container. DS 2-02.2.1.A.32

14. Revise the lot coverage calculation to include the vehicular use area. The allowed lot coverage for this use is 60 percent. Lot coverage includes all structures and vehicular use areas. The allowed and actual floor area ratio must also be listed. Maximum floor area ratio is .40. Revise or as required, all LUC code data information such as required and the number of vehicle-parking and loading zones required and provided, allowed and actual floor area ratio, allowed and proposed building heights, allowed and actual lot coverage. DS 2-02.2.2.A.1 - .6

15. Additional comments may be forthcoming based on the response comments and revised site plan.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and landscape plan and requested documents

Final Status

Task End Date Reviewer's Name Type of Review Description
03/22/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
03/18/2004 SUE REEVES REJECT SHELF Completed