Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00609
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/10/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/12/2004 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate location of fan coil unit FC-1 with the electrical equipment 2. Revise the design of the fuel return line to comply with the requirements of Section 1305.4, IMC 2000. 3. Coordinate the Fuel Tank Detail (sheet M2) with General Notes #4 and #6 4. Provide sequence of operation for the sump pump. |
| 02/12/2004 | JIM TATE | ENGINEERING | REVIEW | Denied | Site Plan approval required. |
| 02/17/2004 | NEAL SAUNDERS | BUILDING-COMMERCIAL | REVIEW | Z_DO NOT USE | |
| 02/17/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Z_DO NOT USE | |
| 02/17/2004 | ASHOFFS1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/19/2004 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |