Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM00596
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2004 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 02/09/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 02/10/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify how the water heater is to be mounted above the ceiling and less than 8'-0" AFF (3/P2) if the room finnish schedule shows the ceiling as 9'-6" AFF. |
| 02/10/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/10/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 02/10/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Coordinate the amount of outside air scheduled for HP-1 (M1) and the amount of outside air called for in the ventilation calculations (M2). |
| 02/11/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/18/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/25/2004 | ROBERT SHERRY | WATER | REVIEW | Approved |