Permit Number: T04CM00596
Parcel: 110102710

Address:
3130 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00596
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2004 LOREN MAKUS ENGINEERING REVIEW Approved
02/09/2004 PATRICIA GEHLEN ZONING REVIEW Approved
02/10/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify how the water heater is to be mounted above the ceiling and less than 8'-0" AFF (3/P2) if the room finnish schedule shows the ceiling as 9'-6" AFF.
02/10/2004 JIM EGAN FIRE REVIEW Approved
02/10/2004 MELISSA POULIN WWM REVIEW Approved
02/10/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Coordinate the amount of outside air scheduled for HP-1 (M1) and the amount of outside air called for in the ventilation calculations (M2).
02/11/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/18/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
02/25/2004 ROBERT SHERRY WATER REVIEW Approved