Permit Number: T04CM00553
Parcel: 13409002E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00553
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed. Based on the recalculated pressure loss calculations, the branch piping sizes shown in detail 1/MP-1 appear to be undersized; revise as required. Reference Section A 6.1, UPC 1994.
06/24/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/25/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Approv-Cond
07/13/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved