Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00553
Parcel: 13409002E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00553
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2004 JIM EGAN FIRE REVIEW Approved
05/13/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Submit an appeal to the Building Official justifying the alternate calculations for the ventilation of the project space. Reference Section 105.2, IMC 2000.
05/13/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Based on the recalculated pressure loss calculations, the branch piping sizes shown in detail 1/MP-1 appear to be undersized; revise as required. Reference Section A 6.1, UPC 1994.
2. Coordinate the size of the building water supply pipe shown on sheet 1 with the size shown on sheets 9 and 11.
05/13/2004 ROBERT SHERRY WATER REVIEW Approved
05/13/2004 GERRY KOZIOL WWM REVIEW Approved
05/20/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied 1) Bathrooms--Provide 3 waterclosets for men and 6 water-closets for women. If waterclosets are provided in another building show them.
2) Specify and note on plans that areas above storage room
and bathrooms will not be used for storage. Provide a sign stating "not a storage area " and locate in conspicuous location.
3) Specify solid blking behind grab bars atbath rooms.
4) Comply to comment #10 of previous comment dated
05/18/04.
05/21/2004 Paul Machado ENGINEERING REVIEW Approved
06/01/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
06/03/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Ckt A-1, with (14) (182W) fixtures, and the two exit lights, should have at least 2548 VA, not 1800.
2. Same as above for Ckt A-3.
3. Circuit 11 has exterior lights in plan view, but is spare on panel schedule. Please clarify.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/04/2004 DELMA ROBEY OUT TO CUSTOMER Completed