Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM00532
Parcel: 133231460

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00532
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/13/2004 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/11/2004 SUE REEVES OUT TO CUSTOMER Completed
02/17/2004 ANGIE SHOFFSTALL APPROVAL SHELF Completed