Permit Number: T04CM00532
Parcel: 133231460

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00532
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise water pipe sizing to accomodate flush valves. Note: 39 fixture units have a demand of approximately 46 gpm in a predominately flush valve system.
02/13/2004 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2004 TAMI ACHONG OUT TO CUSTOMER Completed