Permit Number: T04CM00531
Parcel: 13313006K

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00531
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2004 JIM EGAN FIRE REVIEW Approved
02/05/2004 DAN CASTRO ZONING REVIEW Approved
02/10/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/10/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
02/10/2004 MELISSA POULIN WWM REVIEW Approved
02/10/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/10/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/10/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM00531 DENIED 2/10/04
Feeder load calculations shall count largest motor at 125%.
02/10/2004 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2004 LISA LESNY APPROVAL SHELF Completed
02/10/2004 LISA LESNY OUT TO CUSTOMER Completed