Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00397
Parcel: 14011020B

Address:
2520 E BENSON HY

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM00397
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation for restroom. Reference Table 403.3, IMC 2000.
03/11/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2000, for storage occupancy.
2. Provide fixture descriptions for all plumbing fixtures. Reference Section 103.2.3, UPC 1994.
3. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994.
4. City of Tucson Ordinance 1802 requires a reduced pressure backflow preventer to be located immediately after the water meter. Please show the location and size of the RPBP on the drawings and show the pressure drop on the water calculations.
5. Provide rim elevation of next upstream sanitary manhole. Determine need for backwater valve per Section 710.1, UPC 1994.
6. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 1994.
7. Indicate the inverts of the new building sewer at its points of connection to the building drain and to the HCS as well as its minimum slope. Reference Sections 718.1 and 718.3, UPC 1994.
03/11/2004 ROBERT SHERRY WATER REVIEW Approved
03/12/2004 JIM EGAN FIRE REVIEW Approved
03/25/2004 Doug Williams ENGINEERING REVIEW Denied Building Plans may not be approved prior to Site Plan approval. Listed below are comments that must be addressed prior to Site approval:

SUBJECT: Site review - 2520 E. Benson Highway
DATE: 26 March 2004
ACTIVITY NUMBERS: T04CM00397
T15S, R14E, Section 5

SUMMARY:

Engineering Division has reviewed the Site Plan received on 10 March 2004. This site lies within a designated critical basin. Resubmittal shall include a drainage report addressing critical basin flow reduction requirements (15% minimum reductions in the post-developed 2- 10- and 100-year flow events exiting the site), in accordance with Sections 1.4 and 2.1 of the Pima County/City of Tucson Stormwater Detention/Retention Manual (Development Standards 10-01.0 and 2-02.2 C). The report must also address the minimum contents outlined in section 2.3 of the City of Tucson's Standards Manual for Drainage Design and Floodplain Management (SMDDFM) - Development Standard 10-02.0. Approval of the site plan is not recommended, and may not be, until a drainage report addressing the requirements noted above is approved and the items required for site approval are provided on the plan. Subsequent comments may be necessary upon resubmittal, in order to assure incorporation of retention/detention, and possible floodplain development requirements onsite.

Please address the following comments on the site plan:
1. Depict existing and future sight visibility triangles for the Driveway/Parking Area Access Lane (PAAL) intersecting Benson Highway - a major (Arterial) street - in accordance with Development Standards (DS) 2-02.2.10 & 3-01.5.0 and the City of Tucson's Major Streets and Routes (MS&R) Plan (see redlines on plan).
2. Depict drainage patterns, lowest floor elevation, and proposed finish grades. The elevations provided do not coincide with current elevations/topography available online. For information, visit: http://tdotmaps.transview.org/mapguide_mwf_tdot.htm
3. Provide and label roof drainage direction(s), downspout locations and corresponding sidewalk scuppers for conveyance of drainage under all sidewalk areas (DS 2-08.4.1 E and 2-08.5.1 E).
4. Provide estimated cut/fill quantities (DS 2-02.2.1 A 17).
5. Dimension the existing and future half, or full right of way widths for Benson Highway. Please ensure future intersection widening in accordance with the MS&R Plan is depicted for the MS&R right of way (DS 2-02.2 A 19 & MS&R Plan).
6. All easements of record must be depicted with recording information on the plan (DS 2-02.2 A 20).
7. Dimension from street monument lines to existing and proposed curbs, sidewalks, and utility lines. Include the existing sewer line on, or adjacent to, the southwestern portion of the site (DS 2-02.2.1 A 21).
8. Depict and label the location of major physical features, such the adjacent drainageway (Earp Wash), on the site plan (DS 2-02.2 A 22). Please refer to comment # 10, below. Drainage and maintenance access easements may be required to be dedicated prior to site approval.
9. The plan must depict a dumpster location with an enclosure onsite, or provide written approval from Environmental Services Department for an acceptable alternative. All commercial site developments require an onsite centralized refuse provision with container location, size and access thereto fully labeled and dimensioned on the site plan (DS 2-02.2.1 A 32 an 6-01.0).
10. Additional required information, some drawn from a drainage report, must also be provided on a revised site plan. These include, but are not limited to the following:
a) limits of the 100-year floodplain with water surface elevations at 200' intervals, minimum;
b) 100-year ponding limits/water surface elevation for onsite detention;
c) detention basin maintenance access ramp, a maintenance checklist, and basin responsibility information;
d) erosion hazard setback for Earp Wash;
e) 50' Watercourse Amenities and Safety Habitat (W.A.S.H.) Ordinance Study Area delineation. Please refer to Section 29-12, Tucson Code, for W.A.S.H. Ordinance development requirements. These regulations, and related attachments A-F may be purchased at the City/County Public Works Building on the 3rd floor (Floodplain/City Engineer's Office), or accessed by the following link: http://fws.municode.com/CGI-BIN/om_isapi.dll?infobase=11294.nfo&jump=ch029.x1-29-12&softpage=newTestMainnonFrame#JUMPDEST_ch029.x1-29-12
11. A grading permit may be required for this development. Grading must be in conformance with the 2000 International Building Code (IBC) - local amendment. This document may be accessed at http://www.ci.tucson.az.us/dsd/2000_IBC_Amendments.pdf

GENERAL COMMENTS:
1. Subsequent comments may be necessary upon resubmittal, due to drainage requirements associated with this proposed development.
2. A right of way excavation permit will be required for all proposed work or development activity in the right of way. Contact Permit and Codes Section, Tucson Department of Transportation - Engineering Division at 791-5100 for questions.
Resubmittal will require a revised site plan with a drainage report addressing all of the items listed above.
If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
04/02/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/02/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Show how the overhead door is attached and supported. Specify the size
of beam and its connection.
2) Sheet (1) of the sheets 11 x 17"- cross-referance to correct sheet and detail.
See detail k/3.
3) Regarding the physically handicapped bathroom , the watercloset shall be
16-18" from wall. Show on plans.
4) Provide 2 sets of shop drawings.
04/05/2004 GERRY KOZIOL WWM REVIEW Denied
04/10/2004 PATRICIA GEHLEN ZONING REVIEW Denied Zoning 4/10/2004
Building plans will be reviewed and approved once the site plan is approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/12/2004 LISA LESNY OUT TO CUSTOMER Completed