Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM00376
Parcel: 126042470

Address:
649 N JERRIE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00376
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2004 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM00376

4/19/04 649 N. JERRIE

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.
2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


STRUCTURAL PLANS:

1. PLEASE PROVIDE THE GRADE AND SPECIES OF THE 2 - 2 X 8 BEAM

ELEVATIONS:

1. PLEASE NOTE THE BUILT-UP ROOF IS TO BE A COLD APPLICATION ROOF. SEE PREMIER'S LISTING, PFC-5002 SECTION 2.7.1 .

PLUMBING PLANS:

1. PLEASE RE-CHECK THE LENGTHS FOR THE GAS LINES. THEY CONFLICT WITH THE PLANS.

2. PROVIDE VENTS IN ACCORD WITH THE UNIFORM PLUMBING CODE.

3. THE VALUES USED ON THE "FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH" CHART APPEAR TO BE IN ACCORD WITH THE I.R.C. INSTEAD OF THE UNIFORM PLUMBING CODE.


MECHANICAL PLANS:

1. THE RETURN AIR IS PROHIBITED TO BE TSKEN FROM A CLOTHES CLOSET. SEE R1602 .

ELECTRICAL PLANS:

1. THE LAVATORY RECEPTACLE IS REQUIRED TO BE ON A DEDICATED CIRCUIT. SEE E3603.4 .

2. SMOKE DETECTORS ARE REQUIRED IN THE AREAS IMMEDIATELY OUTSIDE THE BEDROOMS. SEE R317.1, ITEM 2 .









IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 110


NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC EXCEPT FOR THE PLUMBING PORTION WHICH IS THE STATE PLUMBING CODE. ALL MODEL PLANS SHALL BE REFERENCE TO THE PREVIOUSLY MENTIONED CODES.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2004 LISA LESNY OUT TO CUSTOMER Completed