Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00346
Parcel: 11711096D

Review Status: Completed

Review Details: REVISION

Permit Number - T04CM00346
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM00346 DENIED 4/13/04
1. Original plans were approved under Revision 1 triangle. Water heater has been reconfigured on this Revision, making it Revision 2.
2. Electrical Load Summary for Panel shows 98.6 A on 90A panel. Per the panel schedule, this panel is 100A. Pls clarify.
3. C1 panel schedule shows 50A total. Total comes to 28.2A on Load Summary. Pls clarify.
4. Add WH to Load Summary.
04/13/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2004 LISA LESNY OUT TO CUSTOMER Completed