Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T04CM00346
Review Name: REVISION
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/13/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM00346 DENIED 4/13/04 1. Original plans were approved under Revision 1 triangle. Water heater has been reconfigured on this Revision, making it Revision 2. 2. Electrical Load Summary for Panel shows 98.6 A on 90A panel. Per the panel schedule, this panel is 100A. Pls clarify. 3. C1 panel schedule shows 50A total. Total comes to 28.2A on Load Summary. Pls clarify. 4. Add WH to Load Summary. |
04/13/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/13/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |