Permit Number: T04CM00335
Parcel: 11105026C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T04CM00335
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2004 ANY BUILDING-COMMERCIAL REVIEW Z_DO NOT USE
01/27/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/27/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/27/2004 JIM EGAN FIRE REVIEW Approved
01/27/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM00335 DENIED 1/27/04
1. Provide cut sheet for new lights.
2. Indicate net electrical load changes.
3. If the intent is to use the existing circuit now powering the lights slated for removal, state so on the plans.
4. Provide a panel load calculation as necessary. See Comment #2 above.