Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM00334
Parcel: 11004345C

Address:
3215 N SWAN RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00334
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Provide structural calculations for proposed structure or design to the conventional requirements per section 2308 IBC. Note: Rafters can not span more than 24", ledger size to be the same as the depth of the cut of the rafter, roof sheathing/planking to be installed as per sections 2308.10.8 & 9 IBC. Please change detail to 24" o.c. as well. Provide shear value of 1x strips indicated on plan. If rafter is not to be fully supported by the ledger, provide sizing of member for actual rafter dimension supported. i.e.: next size per tables is a 2 x 4.
2. Show how counter flashing at wall/ roof connection is to be achieved. Caulking without counter flashing is not an acceptable method. Revise plans.
3. Provide distance to property line for determination of fire resistance rating of exterior walls. Reference Table 602 IBC. If columns are less than 10 feet from the property line, provide detail and listing for one-hour construction. Unaware of an approved listing for fire retardant treated wood. Provide listing and detail in order to comply with requirements of Table 602 IBC, also see definition of a building, section 502.1 IBC.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/01/2004 TAMI ACHONG OUT TO CUSTOMER Completed
02/27/2004 ANGIE SHOFFSTALL REJECT SHELF Completed