Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM00334
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/09/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations for proposed structure or design to the conventional requirements per section 2308 IBC. Note: Rafters can not span more than 24", ledger size to be the same as the depth of the cut of the rafter, roof sheathing/planking to be installed as per sections 2308.10.8 & 9 IBC. 2. Show how counter flashing at wall/ roof connection is to be achieved. 3. Provide distance to property line for determination of fire resistance rating of exterior walls. Reference Table 602 IBC. If columns are less than 10 feet from the property line, provide detail and listing for one-hour construction. |
02/10/2004 | MELISSA POULIN | WWM | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/10/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |
02/10/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |