Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM00334
Parcel: 11004345C

Address:
3215 N SWAN RD

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM00334
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Provide structural calculations for proposed structure or design to the conventional requirements per section 2308 IBC. Note: Rafters can not span more than 24", ledger size to be the same as the depth of the cut of the rafter, roof sheathing/planking to be installed as per sections 2308.10.8 & 9 IBC.
2. Show how counter flashing at wall/ roof connection is to be achieved.
3. Provide distance to property line for determination of fire resistance rating of exterior walls. Reference Table 602 IBC. If columns are less than 10 feet from the property line, provide detail and listing for one-hour construction.
02/10/2004 MELISSA POULIN WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2004 EGRANT1 OUT TO CUSTOMER Completed
02/10/2004 ANGIE SHOFFSTALL REJECT SHELF Completed