Permit Number: T04CM00332
Parcel: 10707016D

Address:
1380 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM00332
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Approved
07/19/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied 1. "Provide full design for site lighting on scaled drawing, including location of each pole/luminaire, identification of fixture type and quantity on each pole, and location of conduit runs." This comment was made on the first submittal. Unresponsive. Fixture schedule still calls for pole-mounted lighting, and such lighting is accounted for on the panel schedule and project load calculations.
2. "Same as above for high-rise signs and receptacle." This comment was made on the first submittal. Unresponsive. Such lighting is still accounted for on the panel schedule and project load calculations.
3. "Provide pole and foundation details for all poles." This comment was made on the first submittal. Unresponsive. No such detail on plans.
4. Checked with Mechanical Plans Examiner for Electrical Data on RTUs, since this information was incomplete on the Mechanical Plans. The protective devices are determined to be correctly sized for their respective units. However, the Compressor, Condenser Coil Fan Motor, and Evaporator Blower Motor may be anticipated to operate at the same time. The KVA count on Panel P was evaluated with this in mind, and it appears that the total RTU KVA count is 39.1 KVA with 25% added for the largest motor. With 1.25% demand factor for continuous loads, Interior Lighting totals 3.0 KVA and Exterior Lighting totals 9.9 KVA. Kitchen appears to total 34.3 KVA. Total is 99.2 KVA, or 275.6 A. Please correct.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2004 BETH GRANT OUT TO CUSTOMER Completed
07/26/2004 ANGIE SHOFFSTALL REJECT SHELF Completed