Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM00332
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the trap arm and clarify the size of the fixture for the 4" floor drain under booth at office end which is called out as a 3" floor drain on the riser diagram and is shown with a 3" trap arm. Reference Table 10-1, UPC 1994. 2. Revise the drainage fixture unit schedule using the fixture unit values shown in Table 7.3, UPC 1994. 3. Clarify the loop vent for the hand sink at the dish table. 4. Revise the water system demand using the fixture unit values (Tables 6-3 and A-2) from the 1994 UPC. 5. Provide reduced pressure backflow preventer for the carbonator. Reference Section 603.3.12, UPC 1994. |
| 05/07/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | . |
| 05/26/2004 | EGRANT1 | WWM | REVIEW | Needs Review | |
| 05/26/2004 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 05/26/2004 | EGRANT1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |