Permit Number: T04CM00332
Parcel: 10707016D

Address:
1380 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM00332
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2004 JIM EGAN FIRE REVIEW Approved
01/27/2004 ANY BUILDING-COMMERCIAL REVIEW Z_DO NOT USE
04/16/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise size of trap arm for floor drain located at stretch end of building.
2. Show venting for hand sink at dish table. Show cleanouts.
3.Remove note calling for the drain line to be sized "by code" and state the required size.
4. Show table of waste fixture units fo project. Note if new fixtures are replacing existing fixtures.
5. Floor receptor in Mechanical room should not be connected to grease waste line.
6. Revise location of Equipment note #69 from floor drain to floor receptor.
7. Show listing information for grease trap.
8. Remove urinal if not desired by owner.
9. Provide trap primers for floor drains at stretch end, in commissary and along the glass wall.
10. Provide cleanout for commissary floor drain and all horizontal drain lines greater than 5' from the main waste line.
11. Provide cleanouts for all sinks.
12. Include ALL plumbing fixtures in the water demand calculations.
13. Verify size of meter, backflow preventer, and supply pipe.
14. Coordinate water heater piping diagram with sanitary floor plan. (Hub drains not allowed.)
15. Provide backflow protection for all kitchen appliances (including ice machines) directly connected to the water system.
04/16/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
04/16/2004 ROBERT SHERRY WATER REVIEW Approved
04/16/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/16/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show size, route, and termination of condensate drains from HVAC equipment.
2. Condensate drain from walk-in cooler and freezer may not terminate where surface runoff can occur.
3. Provide ventilation to prep area per Table 403.3, IMC 2000.
4. Tucson is using the 2000 International Mechanical Code.
5. Provide interconnection of the kitchen hood with the rooftop units providing make-up air.
6. Increase the exhaust flow through the hood to conform to the requirements of Section 507.13.3, IMC 2000, or present listing information for the hood that shows a lower cfm.
05/07/2004 LLESNY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/07/2004 LLESNY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/07/2004 LISA LESNY OUT TO CUSTOMER Completed